Problem

Cause

Remedy

Water pump will not 1. Scale on probes

Check and clean or replace as necessary.

come on at times

2. Bad Pump Contactor

Check to see if contactor is being powered.

Check to see if contactor coil is pulling in. Replace if

necessary.

3. Bad Pump Motor

Check the incoming power to the pump to be sure it

is receiving power. If power is present but motor does

not run, replace it.

Low Fuel pressure

1. Gas pressure regulator

Check and replace.

Boiler Flooding

1. Pump does not shut off

Dirty probes. Clean or replace as necessary.

2. Relay failed

Make sure relay is plugged in tightly. If so, replace

water level relay.

3. Ground Connection

Check for tightness and clean.

4. Vacuum created with

As the boiler cools off, it pulls water from the system

boiler off

piping. To prevent this, add a 1/4” check valve on the

steam gauge assembly piping, which closes under

pressure and opens under vacuum.