Description/instructions, Condensate return tank – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual

Page 39

Advertising
background image

32-G 1/01

Description/Instructions

Vent

Vent

Return

Cold
Water
Supply

Sight

Glass

Union

Pump/

Strainer

Thermometer

Aquastat

Drain

Condensate

Return

Tank

Blowdown

Separator

Outlet
To Drain

Check

Valve

Shut

Off

Valve

Cold Water
Inlet

Basic Boiler,

Condensate Tank,

and Blow off

Separator

NOTE

Where a condensate return tank is

to be fitted, this should:
1) Be vented to a safe

location, and
2) Have a capacity sufficient to

satisfy boiler consumption as well

as maintain proper return tank

temperature.

3) Vent pipe should not be down-

sized (this may cause pressure

build up in the condensate tank).
4) Return pipes must not be insu-

lated. This can cause overheating

the return system, causing a vapor

lock in the pump.
5) See Return System Instruction

Manual for detailed instructions.