Maintenance – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual

Page 66

Advertising
background image

57-G 1/01

Maintenance

g) Remove brass pipe plug at the

cross connection below water column

and clean nipple into boiler. Boiler

must be cold and water level below

pipe.

Remove plug at cross section; clean

nipple to boiler.

Recommended Semi-Annual

Maintenance Schedule

a) Cleaning the gas burner

assembly
1)
Disconnect the gas head from the

burner by disconnecting the union.

Remove the burner plate screws. For

4-15 HP boilers with scanner, discon-

nect scanner from burner plate.

Withdraw the burner assembly and

clean the flame rod and ignition elec-

trode.
2) Check that the settings of the

flame rod, if applicable, and ignition

electrode correspond to those in the

illustration below.
3) Reassemble the burner assembly

and check the flame rod setting or

scanner setting.
4) Check the combustion efficiency of

the burner and adjust if necessary.
5) Clean probe on top of boiler shell

and probes in water column. There

must be no pressure on the boiler dur-

ing the removal of the probes.
6) Check refractories for soot or

breakage and inspect the stainless

steel ring (50 and 60 HP only).
7) With the boiler under no more

than 15 PSI pressure, check that the

steam safety valve is operating by

lifting the lever.
b) Drain condensate tank and clean

tank by flushing with hose. Check

float valve operation.
c) Check electrical controls and

motors for correct operation.

d) Check water pump for correct

operation.
e) Shut off the boiler completely

and drain.
f) Remove the hand holes and

inspect the interior of the vessel for

scale or sludge deposits. The

amount of deposits will indicate the

efficiency of the water treatment being

used. The frequency of the inspection

will depend on the condition of the

water side of the boiler.

Gap to Pipe
1/8"

±

1/16"

Gap to Pipe
1/8"

±

1/16"

(Ignition Gap)

Test

Pressure

Tapping

Flame Rod

Orifice

Pipe

Grounding

Fins

Ignition Electrode

Ignition Electrode
Holder

Burner
Plate

Gas Burner Ignition
Electrode gap setting is same on 4 - 100 HP units
whether Flame Rod or Scanner is utilized.

Inspect hand holes for scale or sludge

buildup.