Maintenance – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual

Page 72

Advertising
background image

63-G 1/01

Maintenance

Problem

Cause

Remedy

Pump runs but does

1. Vapor locking of pump.

Allow system to cool down, check steam traps

not put water into boiler

and check to be sure return lines are not insulated. Check

return tank temp. If it is above 180 deg. F, (82 deg. C)

vapor locking of pump will occur. Inspect check valves.

Clean and replace as needed. Replace pump with

multistage centrifugal good for 250 degrees F (121 deg.C).

2. Impeller Adjustment

Check for impeller wear and adjust per component

information in instruction manual (Burks only).

3. Back pressure on pump

Need to install repair kit on pump.

4. Plugged feed water

Check and clean or replace as necessary.

nipple

Water pump will not

1. Scale on probes.

Check and clean or replace as necessary.

come on at times.

2. Bad Pump Contactor

Check to see if contactor is being powered.

Check to see if contactor coil is pulling in. Replace if

necessary.

3. Bad Pump Motor

Check the incoming power to the pump to be

sure it is receiving power. If power is present but motor

does not run, replace it.

Low Fuel pressure

1. Gas pressure regulator

Check and replace.

Boiler Flooding

1. Pump does not

Dirty Probes. Clean or replace as necessary.

shut off

2. Relay failed

Make sure relay is plugged in tightly. If so,

replace water level relay.

3. Ground Connection

Check for tightness and clean.

4. Vacuum created with

As the boiler cools off, it pulls water from the system

boiler off.

piping. To prevent this, add a 1/4" check valve on the

steam gauge assembly piping, which closes under

pressure and opens under vacuum.

Advertising
This manual is related to the following products: