Operation

Gas Burner Set Up For Boilers

Equipped with High-Low-Off
a)
A gas fired burner equipped for

high-low-off firing is available as an

option on Fulton gas fired steam

boilers for 30 -100 HP units only.
b) Boilers that have a high-low-off

firing rate will have a linkage

between the high-low gas valve and

the primary air gate. This valve is

equipped with a spring return.
c) The linkage will be disconnected

from the gas valve for shipment.
d) Mount the gas train on the pipe

nipple of the burner plate with the

gas train inlet directly facing over the

panel box. Reconnect the linkage

from the primary air gate to the high-

low gas valve.
e) The end of the linkage arm that

goes to the gas valve will have a

notch on both sides of where the

swivel collar should be centered.

This setting was based on factory

test fire conditions.
f) Combustion analysis should be

done at the installation to make any

changes to insure proper combus-

tion characteristics.
g) To adjust the linkage, unscrew

the swivel collar and move the link-

age rod in the appropriate direction.

The high-low-off configuration comes

with two operating pressure controls.
h) Set the low operating pressure

control to approximately 60% of your

desired set point and the main oper-

ating pressure control to your

desired set point.

Gas burner equiped with high-low-off firing

Panel Box for Boilers equiped with high-low-off firing

Low firePressure Control

Night Heating Pressure Control (Optional)