Problem

Cause

Remedy

Flame Failure

5. Scanner

Check for dirt on flame scanner and clean. Check for

proper location of detector.

6. Flame Safeguard Control

Check voltage at terminal leading to main gas valve.

If no power, replace the control.

7. Loose wire at fuel

Tighten wiring connections.

valve circuit

8. Contact open on air

Adjust to proper setting.

safety switch

9. Scanner wiring reversed

Change to correct terminals.

at panel box

Burner Cut-Off

1. Power Supply

Check fuse or circuit; reset or replace, as necessary.

2. Gas Supply

Check to be sure main gas cock is not closed. Check coil

in gas valve with OHM meter. Replace if faulty. Check gas

regulator setting and readjust as necessary. Check inlet

gas pressure and increase or decrease as necessary.

3. Ignition Electrodes

Check electrodes for carbon buildup and clean if

necessary.Check for proper adjustment. Readjust if

necessary. Check for cracks in porcelain; if found, replace.

4. Scanner

Check for dirt on flame scanner and clean.

Check for proper location of detector.

5. Air Switch

Check for bad air switch by jumpering the two air switch

leads as the terminal block. If the boiler starts and runs

with these terminals jumpered, the air switch should be

replaced.

6. Gas Valve Sticking

Check for dirt in valve or orifice and clean if necessary.

(Pilot)

Check for faulty actuator or valve and replace if necessary.

7. Weak Amplifier

Replace.

8. Weak Pilot

Adjust to larger pilot by adjusting pilot gas pressure

regulator.

9. Faulty Liquid Level Control Check to see if there is power to terminal number 10

when the sight glass shows the proper water level.

If there is no power at this terminal, the control is bad and

must be replaced.

10. Dirty or defective

Clean or replace.

UV Scanner