Description/instructions – Fulton Edge ICX or FB-F Vertical Tubeless Boilers (Steam), Gas Fired User Manual

Page 48

Advertising
background image

41-G 1/01

Description/Instructions

Exhaust Side Wall Venting (UL and

MEA Approved- MEA File Number

68-79-E Vol. 2

)

a) Boilers for which sidewall venting

may be utilized are No. 2 oil, natural

gas, or combination No. 2 oil and nat-

ural gas,sizes 4 to 30 H.P. The fol-

lowing criteria is required for installa-

tions using sidewall venting:
1) Flue vent piping shall be pitched

upward at 1/4" per foot of length.
2) A U.L. Approved draft fan must be

installed to provide sufficient draft

(-.02 to -.04 inches WC pressure -

0.508 to -1.016 mm) to safely vent

the products of combustion.
3) The draft fan should be located as

close to the flue outlet as possible.
4) Draft regulation sufficient to

lower the draft to between -.02 and

-.04 inch WC pressure (-.508 to -

1.016mm) may be required. The

draft regulator(s) must be between

the boiler and draft fan.
5) The draft fan shall have an air flow

proving switch wired in series with the

boiler air safety switch.
6) The sidewall vent total length from

boiler exhaust to termination shall not

exceed 35 feet (10.7 m) with 4

elbows maximum.

Combustion Air Intake (UL and

MEA Approved- MEA File Number

68-74-E Vol. 3

)

a) Vertical boilers as described in

MEA 68-79-E Vol. 3 applied with

combustion air intake assembly. This

shall be applicable only to gas fired

units, sizes 4-30 boiler horsepower.

The following criteria is required for

installations using combustion air

intake assemblies.
1) Outside air intake inlet shall be

equipped with a vent cap in order to

prevent flame blow out from exces-

sive wind. This vent cap shall have a

minimum cross sectional opening

equal to an 8 inch vent pipe.
2) All intake ducting shall have a

cross sectional area equal to or

greater than 50 square inches.
3) A mesh screen shall be affixed to

the air inlet with openings of approxi-

mately 1/2" x 3/4".
4) The total length from outdoors

to the boiler intake shall not exceed

35 feet (10.7 m) with four elbows

maximum.
Corrosion of flue pipe
a)
In the case of a combustion flue

pipe, acid may develop over a long

period of time by the following

process. Chlorine containing gases,

such as halocarbon refrigerants, car-

bon tetrachloride, trichloroethylene,

or perchloroethylene, when drawn

into combustion air are broken down

into elemental chlorine gas which

exits up the flue pipe. If the flue pipe

is cold, as it would be if the combus-

tion process had been off for some

time, the water vapor condenses in

the flue pipe during the first few min-

utes of ignition and the chlorine in the

combustion gas dissolves in the

water forming hydrochloric acid. As

the combustion system flue line

increases in temperature, the water

vapor no longer condenses because

the flue temperature is above the dew

point of the combustion gas.

The combustion gas then dries

out (dehydrates) the hydrochloric

acid solution leaving behind dry

chloride salt.
b) When the next cold start-up

occurs, the process repeats except

that more and more chloride collects

and concentrates along the flue. As

the quantity of chloride increases it

does not dehydrate completely as the

flue heats up and a corrosive poultice

develops which attacks the steel and

will also attack the boiler.
c) Concentration levels of only a

few ppm of chlorine containing

compounds in combustion air can

produce serious corrosion over long

periods of time. High chlorine con-

taining compounds such as carbon

tetrachloride or perchloroethylene

would be prime suspects .

Air Flow
Safety Switch

U.L. Approved
Induced Draft Fan

Side Wall

Vent

Termination

(By Others)

Side Wall Vent
(By Others)

Advertising
This manual is related to the following products: