Conventional Venting
a)
The stack should rise continuously

to the connection with the chimney,

and should contain no more than two

bends at 45 angles or less. If required

as the result of space limitations, one

90 elbow can be fitted at the back of

the boiler. There should be two feet of

straight, horizontal flue before any

bends or turns. Any alternative stack

arrangement must supply a negative

.02 to.04” W.C. pressure (0.508 to

1.016 mm) with the burner off.
b) The run in the total distance of

stack ducting, as measured in a

straight line from the outlet of the

boiler to the outlet of the stack,

should not exceed 25% of the rise.

With the exception of a duct run

described in Item a, horizontal sec-

tions of ducting must be avoided,

and should not exceed four feet of

total run.

c) The stack and chimney material

shall comply with all local codes.
d) Adequate provision must be

made for the support of the weight of

the chimney and stack to avoid hav-

ing too great a load imparted to the

flue outlet connection of the boiler.
e) The proper flue size and draft

control is most important for proper

burner operation. The flue must be as

large or larger than the outlet on the

boiler. Avoid flue piping and elbows

by placing the boiler as close as pos-

sible to the chimney.
f) A mechanical draft regulator

should be installed in the flue

outlet. Do not install the draft regu-

lator prior to the first turn of the flue.

BHP

Boiler Flue Size

Inches Millimeters

6

6

152

9.5

6

152

10

6

152

15

8

203

20

10 254

30

12

305

40

12

305

50

12

305

60

12

305

g) The installer should check the

draft with a meter at negative .02 to

.04” W.C. pressure (0.508 to 1.016

mm) with the burner off.

Roof

Minimum

6' Above

Any Structure

Within 30'

Support As

Necessary

Install
Appropriate
Weather
Cap

Horizontal
Run 2'

Draft Regulator
(If Necessary)

Draft Regulator
(If Necessary)

Expansion Joints
As Required

Horizontal
Run 2'

Cleanout

Door

60°

(45° Min.)

Cleanout

Door

Cleanout

Door

This Distance
Must Not
Exceed 25%
Of Total Rise

Baffle

3'

3'

30°

Max

Stagger

Entrances

A

A

A-A

Total

Rise