Problem

Cause

Remedy

Boiler is Surging

1. Steam traps blowing

Check traps to see if they are clean or replace as necessary.

through

2. Perc (cleaning solvent

Clean boiler with washing soda per instruction manual.

in boiler)

3. Scale build-up or lime

Call water treatment professional and consult factory.

deposits

4. Too much compound in

Dump return tank and flush system. Have water tested by

system (water treatment)

water treatment company.

5. Too much water

Have water tested by water treatment company.

softener (high PH)

6. Too much of a load

Check total equipment horsepower required against

horsepower of boiler being used. Decrease amount of

equipment being used at one time.

7. Boiler new (not

Clean per instructions in instruction manual.

cleaned)

Boiler Rumbles and 1. Draft problem

Check draft with a gauge. Draft should be a -.02” to -.04”

Pulsates

W.C. with burner off or -.04” to -.06” when operating. May

need to install a barometric damper.

Boiler pushing water 1. Steam Traps

Chech traps. Clean or replace as necessary.

with the steam

2. Too much boiler

Dump return tank and flush system. Have water

compound

tested by water treatment company.

Pump will not cut off 1. Dirty Probes

Clean or replace as necessary.

2. Relay failed

Make sure relay is plugged in tightly. If so, replace

water level relay.

3. Ground Connection

Check for tightness and clean.

Pump runs but does 1. Vapor locking of pump

Allow system to cool down, check steam traps and check

not put water into

to be sure return lines are not insulated. Check return tank

boiler

temp. If it is above 180°F., (82°C.) vapor locking of pump

will occur. Inspect check valves. Clean and replace as

needed. Replace pump with multistage centrifugal good

for 250°F. (121°C.).

2. Impeller Adjustment

Check for impeller wear and adjust per component

information in instruction manual (Burks only).

3. Back pressure on pump

Need to install repair kit on pump.

4. Plugged feed water

Check and clean or replace as necessary.