35

Installation

Voltage or Current Follower (PCM models)

PCM series drives can be configured to follow a grounded
(non-isolated) voltage or current signal. To configure the
drive to follow a voltage or current signal, connect the
signal leads to the S1 and S2 terminals on TB501. Ensure
that the following jumper terminals are properly set:

JMP501 Input Range Settings

Set jumper in position 1 for 0 - 5 VDC signal input.

Set jumper in position 2 for 0 - 10 VDC signal input.

Set jumper in position 3 for 4 - 20 mA signal input.

JMP502 Input Type

Jumper pins 1 & 2 for Voltage follower mode.

Jumper pins 2 & 3 for Current follower mode.

See Figure 22 on page 36 for jumper locations and terminal
connections.