48

Calibration

ACCELERATION (ACCEL)

1. Set the speed adjust potentiometer to zero (full CCW)

and wait for the motor to come to a stop (or minimum
speed).

2. Set the speed adjust potentiometer or reference signal

to maximum speed (full CW) and note the time the
motor takes to accelerate to maximum speed.

3. If the acceleration time differs from the desired time,

adjust the ACCEL trimpot until the desired time is
reached. Rotating the ACCEL trimpot CW increases the
acceleration time.

DECELERATION (DECEL)

1. Set the speed adjust potentiometer to maximum (full

CW) and wait for the motor to come to maximum speed.

2. Set the speed adjust potentiometer to minimum speed

(full CCW) and note the time the motor takes to
decelerate to minimum speed.

3. If the deceleration time differs from the desired time,

adjust the DECEL trimpot until the desired time is
reached. Rotating the DECEL pot CW increases the
deceleration time.