Vanguard DigiTMR User Manual

Page 12

Advertising
background image

DIGITMR USER’S MANUAL

REV 3

7

1.4 Technical

Specifications

Table 1. DigiTMR Technical Specifications

TYPE Circuit-breaker analyzer

PHYSICAL SPECIFICATIONS 18”W x 7”H x 15”D (45.7 cm x 17.8 cm x 38.1 cm); Weight: less than 19 lbs

(8.6 kg)

INPUT POWER 3 Amps, 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz

DRY-CONTACT INPUTS 3 dry-input channels; each channel detects main and insertion-resistor

contacts

TIMING WINDOWS 1-second, 10-seconds, or 20-seconds

TIMING RESOLUTIONS ±100 micro-seconds @ 1-second duration

±1.00 milli-seconds @ 10-second duration
±2.00 milli-seconds @ 20-second duration

TIMING ACCURACY 0.05% of reading ±0.1 ms @ 1-second duration

DRY-CONTACT CHANNEL

PROTECTION

Fuses protect all isolated power supplies; all contact inputs are grounded
until test; input channels are protected against static discharge

CONTACT DETECTION RANGE Closed: less than 20 ohms; Open: greater than 5,000 ohms

RESISTOR DETECTION RANGE 50 – 5,000 ohms

TRIGGER INPUT VOLTAGE Open/Close: 30 – 300V, DC or peak AC

VOLTAGE SENSING INPUT

RANGE

V1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V
V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC

BREAKER OPERATIONS Initiate Open, Close, Open – Close, Close – Open, Open – Close – Open

BREAKER INITIATE CAPACITY 30A, 250 Vac/dc max

INITIATE CURRENT READING

RANGE

One, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz

TRAVEL TRANSDUCER INPUT 1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.);

Rotary range: 0 – 360 degrees (±0.006 degrees)

CONTACT TRAVEL POINT

DIFFERENCE

Measures “slow-close” contact-point distances; results can be printed

DISPLAY

Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight
and low-light levels

PRINTER

Built-in 4.5-inch wide thermal printer can print both graphic contact travel
waveforms and tabulated test results

INTERNAL TEST RECORD

STORAGE

Stores up to 100 test records and 99 breaker test plans

COMPUTER INTERFACE RS-232C port (19,200 baud)

PC SOFTWARE

Windows

®

XP/Vista-based Circuit

Breaker Analysis

software is included

with purchase price

SAFETY Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92

standards

ENVIRONMENT Operating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-

22°F to +158° F)

OPTIONS Transportation case (available for the DigiTMR and the travel transducers)

WARRANTY One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.

Advertising