Vanguard DigiTMR User Manual

Page 24

Advertising
background image

DIGITMR USER’S MANUAL

REV 3

19

3.2 General

Procedures

The main steps for timing a circuit breaker are listed in Figure 10 below.

Figure 10. DigiTMR General Operating Procedures

NOTE

To reduce the possibility of damaging the DigiTMR due to static discharge in high
voltage substations, it is recommended that one side of the breaker’s bushings be
grounded for the contact channels.

3.3

Timing Breakers in Quick-Shot Mode

The DigiTMR can provide OPEN or CLOSE times only in Quick-Shot Mode. The DigiTMR can
initiate the OPEN or CLOSE tests, and then the test report will show the OPEN or CLOSE coil
current reading and waveform. If the DigiTMR is operated in Quick-Shot mode using the
External Trigger, no coil current reading or waveform will be recorded.

Get Test Results

• View or print tabulated results

• Print graphic results

• Save timing shot

Time Breaker

• Select DigiTMR test

• Operate Breaker

Connect the DigiTMR

• Ground the DigiTMR (see note)

• Connect the DigiTMR cables to the circuit breaker

• Install the transducer and cable

Apply Power

• Turn on the power for the DigiTMR. Once the unit

goes through its start-up cycle, the “Start-Up”
menu will be displayed.

• Perform self test (hook-up test, cable test) if

necessary