Vanguard DigiTMR User Manual

Page 36

Advertising
background image

DIGITMR USER’S MANUAL

REV 3

31

After all of the contacts have been closed, the following screen will be displayed:

Fully close the breaker. When the breaker is at the close position (on latch), press the

[ENTER]

key to find contact wipe.

e. The test results will be printed, and you will be returned to the “START-UP” menu. A

typical “Slow-Close” test results printout is shown in Figure 11.

NOTES

• The “Slow-Close” test report can be saved in the DigiTMR’s EEPROM. Please see

section 3.8.1 for information on how to save test records.

• You can calculate contact stroke by adding the contact touch and contact wipe

distances.

Figure 11. Typical "Slow-Close" Test Results Printout

LIFT BRKR TO CLS POS
THEN PRESS “ENTER”
TO FIND CONTACT WIPE
LIFT TO CLS BRKR NOW

CONTACT 1: CLOSED
CONTACT 2: CLOSED
CONTACT 3: OPEN
LIFT TO CLS BRKR NOW

Advertising