2 function block execution control, 6 block setting, 1 link object – Yokogawa AXFA14G/C User Manual

Page 19: Function block execution control -5, Block setting -5, Link object -5, Set the parameter for function block vfd, Set link objects as shown in table 4.7

Advertising
background image

IM 01E20F02-01E

4-5

4. CONFIGURATION

T0404-2.EPS

13

FasDllSubscriber
SynchronizationDlcep

Not used for AXF.

14

FmsVfdId

Sets VFD for AXF to be
used.

0x1: System/network

management VFD

0x1234: Function block

VFD

15

FmsMaxOutstanding
ServiceCalling

Set 0 to Server. It is not
used for other applications.

16

FmsMaxOutstanding
ServiceCalled

Set 1 to Server. It is not
used for other applications.

17

FmsFeatures
Supported

Indicates the type of
services in the application
layer. In the AXF, it is
automatically set according
to specific applications.

Sub-

index

Parameter

Description

12

FasDllSubsriberTime
WindowSize

Not used for AXF.

33 VCRs are factory-set as shown in the table below.

Table 4.5

VCR List

Index

(SM)

VCR

Number

Factory Setting

293

For system management (Fixed)

1

294

Server (LocalAddr = 0xF3)

2

295

Server (LocalAddr = 0xF4)

3

296

Server (LocalAddr = 0xF7)

4

297

Trend Source (LocalAddr = 0x07,
Remote Address=0x111)

5

298

Publisher for AI (LocalAddr = 0x20)

6

299

Alert Source (LocalAddr = 0x07,
Remote Address=0x110)

7

300

Server (LocalAddr = 0xF9)

8

301 to 315

Not used.

9 to 33

T0405.EPS

4.5.2 Function Block Execution Control

According to the instructions given in Section 4.3, set
the execution cycle of the function blocks and schedule
of execution.

4.6 Block Setting

Set the parameter for function block VFD.

4.6.1 Link Object

A link object combines the data voluntarily sent by the
function block with the VCR. The AXF has 40 link
objects. A single link object specifies one combination.
Each link object has the parameters listed in Table 4.6.
Parameters must be changed together for each VCR
because the modifications made to each parameter may
cause inconsistent operation.

Table 4.6

Link Object Parameters

T0406.EPS

Sub-

index

Parameters

Description

1

LocalIndex

Sets the index of function
block parameters to be
combined; set “0” for Trend
and Alert.

2

VcrNumber

Sets the index of VCR to
be combined. If set to “0”,
this link object is not used.

3

RemoteIndex

Not used in AXF. Set to “0”.

5

StaleCountLimit

Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to “2” or more.

4

ServiceOperation

Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend

Set link objects as shown in Table 4.7.

Table 4.7

Factory-Settings of Link Objects (example)

T0407.EPS

Index

Link Object #

Factory Settings

30000

AI.OUT

→ VCR#6

1

30001

Trend

→ VCR#5

2

30002

Alert

→ VCR#7

3

30003 to

30039

Not used

4 to 40