A4.6 faqs – Yokogawa AXFA14G/C User Manual

Page 90

Advertising
background image

IM 01E20F02-01E

A-31

APPENDIX 4. LINK MASTER FUNCTIONS

Element

Description

Sub-

index

Size

[bytes]

2


4


2

Indicates the version number of
the LAS schedule downloaded
to the corresponding domain.

Indicates the macro cycle of the
LAS schedule downloaded to
the corresponding domain.

Indicates the time resolution
that is required to execute the
LAS schedule downloaded to
the corresponding domain.

Version

Macrocycle
Duration

TimeResolution

1


2


3

TA0414.EPS

(15)Domain

Read/write: impossible; get-OD: possible

Carrying out the GenericDomainDownload command
from a host writes an LAS schedule to Domain.

CAUTION

When downloading a LAS schedule to AXF,
maximum allowable linkages between devices
are 18.

A4.6 FAQs

Q1.

When the LAS stops, an AXF does not back
it up by becoming the LAS. Why?

A1-1. Is that AXF running as an LM? Check that the

value of BootOperatFunctionalClass (index 367)
is 2 (indicating that it is an LM).

A1-2. Check the values of V(ST) and V(TN) in all

LMs on the segment and confirm that the
following condition is met:

AXF

Other LMs

V(ST)

ϫV(TN)

<

V(ST)

ϫV(TN)

Q2.

How can I make an AXF become the LAS?

A2-1. Check that the version numbers of the active

schedules in the current LAS and the AXF are
the same by reading:

LinkScheduleListCharacteristicsRecord (index
374 for an AXF)

- ActiveScheduleVersion (subindex 3)

A2-2. Make the AXF declare itself as and become the

LAS by writing:

• 0x00 (false) to

PrimaryLinkMasterFlagVariable in the current
LAS; and

• 0xFF (true) to

PrimaryLinkMasterFlagVariable (index 364)
in the AXF.

Q3.

On a segment where an AXF works as the
LAS, another device cannot be connected.
How come?

A3-1. Check the following bus parameters that

indicate the bus parameter as being the LAS for
the AXF and the capabilities of being the LAS
for the device that cannot be connected:
• V(ST), V(MID), V(MRD) of AXF:

ConfiguredLinkSettingsRecord (index 369)

• V(ST), V(MID), V(MRD) of problematic

device: DlmeBasicInfo

Then, confirm that the following conditions are
met:

AXF

Problematic

Device

V(ST)

>

V(ST)

V(MID)

>

V(MID)

V(MRD)

>

V(MRD)

A3-2. Check the node address of the problematic

device is not included in the V(FUN)+V(NUN)
of the AXF.

Advertising