8. PARAMETER LISTS

8.

PARAMETER LISTS

Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S:

Write enabled in O/S mode.

MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

8.1

Resource Block

T0801-1.EPS

Write

Mode

Explanation

Factory

Default

Relative

Index

Parameter Name

Index

Information on this block such as Block Tag, DD Revision,
Execution Time etc.

The revision level of the static data associated with the resource
block. The revision value is incremented each time a static
parameter value in this block is changed.

The user description of the intended application of the block.

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.

The identification number of the plant unit. This information may
be used in the host for sorting alarm, etc.

The actual, target, permitted, and normal modes of the block.

This parameter reflects the error status associated with the
hardware or software components associated with a block.
It is a bit string, so that multiple errors may be shown.

State of the resource block state machine.

Read/write test parameter-used only for conformance testing
and simulation.

String identifying the tag of the resource which contains the
Device Description for this resource.

Manufacturer identification number-used by an interface device
to locate the DD for the resource.

Manufacturer's model number associated with the resource-used
by interface devices to locate the DD file for the resource.

Manufacturer revision number associated with the resource-used
by an interface device to locate the DD file for the resource.

Revision of the DD associated with the resource-used by an
interface device to locate the DD file for the resource.

Options for controlling access of host computer and local control
panels to operating, tuning and alarm parameters of the block.

The types of hardware available as channel numbers.
bit0: Scalar input
bit1: Scalar output
bit2: Discrete input
bit3: Discrete output

Allows a manual restart to be initiated. Several degrees of
restart are possible. They are 1:Run, 2: Restart resource,
3:Restart with initial value specified in FF functional spec. (*1),
and 4: Restart processor.
*1: FF-891 Foundation

TM

Specification Function Block

Application Process Part 2.

Used to show supported resource block options.

0 1000

Block

Header

TAG="RS"

O/S

1 1001

ST_REV

0

-

2 1002

TAG_DESC

Spaces

Auto

3 1003

STRATEGY

1

Auto

4 1004

ALERT_KEY

1

Auto

5 1005

MODE_BLK

Auto

Auto

6 1006

BLOCK_ERR

0

-

7 1007

RS_STATE

-

-

8 1008

TEST_RW

0

Auto

13 1013

DD_REV

1

-

14 1014

GRANT_DENY

0x00

Auto

15 1015

HARD_TYPES

-

16 1016

RESTART

1

Auto

17 1017

FEATURES

0x000a

-

9 1009

DD_RESOURCE

Spaces

-

10 1010

MANUFAC_ID

0x594543

-

11 1011

DEV_TYPE

0x000b

-

12 1012

DEV_REV

-

Advertising