APPENDIX 3. ARITHMETIC (AR) BLOCK

A3.2.3 INPUT_OPTS

INPUT_OPTS has an option that handles an input with
“uncertain” or “bad” status as a “good” status input.

Bit

0

1

2

3

4

5

6

7

8 to 15

TA0302.EPS

Function

Handles IN as a “good” status input if its status is “uncertain.”

Handles IN_LO as a “good” status input if its status is “uncertain.”

Handles IN_1 as a “good” status input if its status is “uncertain.”

Handles IN_1 as a “good” status input if its status is “bad.”

Handles IN_2 as a “good” status input if its status is “uncertain.”

Handles IN_2 as a “good” status input if its status is “bad.”

Handles IN_3 as a “good” status input if its status is “uncertain.”

Handles IN_3 as a “good” status input if its status is “bad.”

Reserved

There are options called “IN Use uncertain” and
“IN_LO Use uncertain” for the IN and IN_LO inputs.
When these options are valid, IN and IN_LO are
internally interpreted as “good” IN and IN_LO even if
their statuses are “uncertain.” (There is no option for
“bad” status.)

For the IN_1, IN_2, and IN_3 auxiliary inputs, there
are options known as “IN_i Use uncertain” and “IN_i
Use bad.” If these options are valid, an IN_i with
“uncertain” or “bad” status is internally interpreted as a
“good” IN_i.

* The exception is that if the input status is “Bad. Not

Connected,” INPUT_OPTS does not apply and the
input is considered “bad” as is.

A3.2.4 Relationship between the Main

Inputs and PV

The value and PV status are determined by the statuses
of two main inputs, INPUT_OPTS, and RANGE_LO
and RANGE_HI.

· If the statuses of two main inputs are both “good” or

anything other than “good”
See A4.2.1, Main Inputs.

· If only one of two main inputs has “good” status after

application of INPUT_OPTS, the PV value is
determined as

follows:

· If the status of IN is “good” and that of “IN_LO”

is anything other than “good”

IN > RANGE_LO

→ PV = IN

IN

Ϲ RANGE_LO

→ See A3.2.1.

· If the status of IN is anything other than “good”

and that of “IN_LO” is “good”

IN_LO < RANGE_HI

→ PV = IN_LO

IN_LO

м RANGE_H

→ See A3.2.1.

RANGE_LO

RANGE_HI

PV = IN_LO

PV = IN

PV = g

ϫ IN + (1-g) ϫ IN_LO

PV = g

ϫ IN + (1-g) ϫ IN_LO

IN

IN_LO

FA0303.EPS

If the status of IN is “good” and that of “IN_LO” is
anything other than “good”

If the status of IN is anything other than “good”
and that of “IN_LO” is “good”