2. ABOUT FIELDBUS

2.

ABOUT FIELDBUS

2.1 Outline

Fieldbus is a widely used bi-directional digital communi-
cation protocol for field devices that enable the simulta-
neous output to many types of data to the process
control system.

The AXF Series Fieldbus communication type employs
the specification standardized by The Fieldbus Founda-
tion, and provides interoperability between Yokogawa
devices and those produced by other manufacturers.
Fieldbus comes with software consisting of AI, DI, IT,
AR and optional PID function blocks that enable the
flexible implementation of systems.

For information on other features, engineering, design,
construction work, startup and maintenance of
Fieldbus, refer to “Fieldbus Technical Information” (TI
38K03A01-01E).

2.2 Internal Structure of AXF

The AXF contains two Virtual Field Devices (VFD)
that share the following functions.

2.2.1 System/network Management VFD

• Sets node addresses and Physical Device tags (PD

Tag) necessary for communication.

• Controls the execution of function blocks.
• Manages operation parameters and communication

resources (Virtual Communication Relationship:
VCR).

2.2.2 Function Block VFD

(1)Resource block

• Manages the status of AXF hardware.
• Automatically informs the host of any detected

faults or other problems.

(2)Transducer block

• Converts the flow sensor output to the volumetric

flow rate signal, and transfers to the AI function
block.

• Transfers limit switch signals to DI function blocks.
• Adhesion diagnosis levels are set and monitored.

(3)AI function blocks

• Condition raw data from the transducer block,

including scaling and damping (with a first-order
lag), and allow input simulation.

• Outputs volumetric or mass flow rate signals.

(4)DI function blocks (two)

• Limit switches for the flow rate and adhesion alarm,

warning.

(5)IT function blocks (two)

• Add two main inputs and integrate them for output.

(6)AR function block

• Switches two main inputs of different measurement

ranges and combines the result with three auxiliary
inputs through the selected compensation function to
calculate the output.

(7)PID function block (optional)

• Performs the PID control computation based on the

deviation of the measured value from the setpoint.

2.3 Logical Structure of Each

Block

PID function

block (option)

F0201.EPS

AXF
Fieldbus

System/network management VFD

Function block VFD

Link Master

PD Tag

Resource block

Block tag

Parameters

Communication

parameters

VCR

Node address

Function block

execution schedule

AR function

block

IT function

block

IT function

block

AI function

block

DI function

block

Sensor

input

Output

SENSOR

Transducer block

Block tag

Parameters

DI function

block

Block tag

OUT_D

Parameters

Sensor

Figure 2.1 Logical Structure of Each Block