2 trend object, 3 view object, Trend object -6 – Yokogawa AXFA14G/C User Manual

Page 20: View object -6

Advertising
background image

IM 01E20F02-01E

4-6

4. CONFIGURATION

F0405.EPS

SMIB

(System
Management
Information
Base)

NMIB

(Network
Management
Information
Base)

AI OUT

FBOD

Alert

Trend

VCR

DLSAP
DLCEP

Fieldbus Cable

AXF

0xF8 0xF3 0xF4 0xF7 0xF9 0x20 0x21 0x07

#1

#2

#3

#4

Resource
block

Transducer
block

Host 1

Host 2

Device 1

Device 2

Link
object

#1

#2

#3

#4

#5

#6

#7

#8

#9

DI2 OUT

DI1 OUT

Figure 4.5 Example of Default Configuration

4.6.3 View Object

This object forms a group of parameters in a block.
One advantage brought by forming groups of param-
eters is the reduction of load for data transactions.
View Object has the parameters listed in Table 4.11 to
4.16. Purpose of View Objects is shown in Table 4.10.

Table 4.10 Purpose of Each View Object

VIEW_1

VIEW_2

VIEW_3

VIEW_4

Set of all the dynamic parameters.

Description

Set of dynamic parameters required by operator
for plant operation. (PV, OUT, Mode etc.)

Set of static parameters which need to be
shown to plant operator at once. (Range etc.)

Set of static parameters for configuration or
maintenance.

T0410.EPS

4.6.2 Trend Object

It is possible to set the parameter so that the function
block automatically transmits Trend. AXF has seven
Trend objects, six of which are used for Trend in
analog mode parameters and one is used for Trend in
discrete mode parameter. A single Trend object
specifies the trend of one parameter.

Each Trend object has the parameters listed in Table
4.8. The first four parameters are the items to be set.
Before writing to a Trend object, it is necessary to
release the WRITE_LOCK parameter.

Table 4.8

Parameters for Trend Objects

T0408.EPS

Sub-

index

Parameters

Description

1

Block Index

Sets the leading index of
the function block that
takes a trend.

2

Parameter Relative
Index

Sets the index of
parameters taking a trend
by a value relative to the
beginning of the function
block. In the AXF AI block,
the following three types of
trends are possible.
7: PV
8: OUT
19: FIELD_VAL

3

Sample Type

Specifies how trends are
taken. Choose one of the
following 2 types:

1: Sampled upon

execution of a function
block.

2: The average value is

sampled.

4

Sample Interval

Specifies sampling
intervals in units of 1/32
ms. Set the integer
multiple of the function
block execution cycle.

5

Last Update

The last sampling time.

6 to 21

List of Status

Status part of a sampled
parameter.

21 to 37 List of Samples

Data part of a sampled
parameter.

Seven trend objects are factory-set as shown Table 4.9.

Table 4.9

Trend Object are Factory-Set

T0409.EPS

Index

Parameters

Factory Settings

32000 to

32007

No setting

TREND_FLT.1 to

TREND_FLT.8

32008 to

32009

No setting

TREND_DIS.1 to

TREND_DIS.2

Advertising