IM 01E20F02-01E

5-5

5. EXPLANATION OF BASIC ITEMS

OUT:

This parameter contains the current measurement value
from Transducer Block or configuration adjusted
engineering unit and the belonging state in AUTO
MODE. OUT contains the value and status set by an
operator in MAN MODE.

Quality

Sub-status

Limit

Alarm

Non-specific

Normal

Active Block Alarm

Block Alarm is Active

Active Advisory Alarm

Advisory Alarm is Active

Active Critical Alarm

Critical Alarm is Active

Unack. Block Alarm

Block Alarm is Unacknowledged

Unack. Advisory Alarm

Advisory Alarm is Active

Good(NC)

Unack. Critical Alarm

0:Not Limited

1:Low Limited

2:High Limited

3:Constant

0:Not Limited

1:Low Limited

2:High Limited

3:Constant

Critical Alarm is Active

Uncertain

Engineering Unit Range
Violation

--

--

Out of sensor operating range

Out of range of min. span and max. span

No-specific

FB board EEPROM failure

TB is O/S

BLOCK_ERR is O/S etc.

Device Failure

EEPROM failure

Internal communication error

Sensor Failure

CPU board failure

Bad

Out of Service

--

RS, AI are O/S

T0503.eps

XD_SCALE:

Scale of input from the transducer block. The maxi-
mum flow rate range on an order sheet is set. "0" (0%),
"10.000"(100%), and "m/s" for the unit are factory-set
unless specified in the order. Changing the unit (can be
set only in flow rate) also causes the unit within the
transducer block to be automatically changed.(The unit
is automatically changed according to the unit selected
in AI. Units which can be set by XD_SCALE are
shown in Table 5.4.1.