8. PARAMETER LISTS

8.3

AI Function Block

T0803-1.EPS

Write

Mode

Explanation

Factory

Default

Relative

Index

Parameter Name

Index

Information on this block such as Block Tag, DD Revision,
Execution Time etc.

The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.

The user description of the intended application of the block

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
Valid range is 0 to 65535.

The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc. Valid range is 1 to 255

The mode parameter is a structured parameter composed of the
target mode, the actual mode, the normal mode and the
permitted mode.
Target: Mode to set the mode of the block
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is

allowed to take.

Normal: Indicates the operating condition that the block will

usually take.

This parameter reflects the error status associated with the
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.

Either the primary analog value for use in executing the function,
or a process value associated with it. May also be calculated
from the READBACK value of an AO block.

The primary analog value calculated as a result of executing
the function.

Allows the transducer analog input or output to the block to be
manually supplied when simulate is enabled. When simulation is
disabled, the simulate value and status track the actual value
and status.

1: Disable, 2: Active

The high and low scale values, engineering units code, and
number of digits to the right of the decimal point used with the
value obtained from the transducer for a specified channel.
Refer to 5.4 AI Function Block Parameters for the units available.

The high and low scale values, engineering units code, and
number of digits to the right of the decimal point to be used in
displaying the OUT parameter and parameters which have the
same scaling as OUT. Refer to 5.4 AI Function Block
Parameters for the units available.

Options for controlling access of host computers and local control
panels to operating, tuning and alarm parameters of the block.

Options which the user may select to alter input and output block
processing.

bit 10: Low cutoff

Options which the user may select in the block processing of status.

bit3: Propagate Fault Forward, bit6: Uncertain if limited,
bit7: Bad if limited, bit 8: Uncertain if Man mode.

The number of the logical hardware channel that is connected to
this I/O block. This information defines the transducer to be used
going to or from the physical world.

1: PV

In the case of AXF, always set 1: Direct. (Note)

Sets low cut point of output. This low cut value becomes
available by setting "Low cutoff" to "IO_OPS".

1 4001

ST_REV

0

-

3 4003

STRATEGY

1

Auto

4 4004

ALERT_KEY

1

-

5 4005

MODE_BLK

Auto

bit

Auto

6 4006

BLOCK_ERR

0

-

7 4007

PV

0

-

8 4008

OUT

0

-

9 4009

SIMULATE

1:

Disable

Auto

10 4010

XD_SCALE

O/S

13 4013

IO_OPTS

0x0000

O/S

14 4014

STATUS_OPTS

0x0000

O/S

15 4015

CHANNEL

1

O/S

16 4016

L_TYPE

1:

Direct

Man

17 4017

LOW_CUT

0

Auto

Time constant of a single exponential filter for the PV, in seconds.

18 4018

PV_FTIME

0

Auto

11 4011

OUT_SCALE

O/S

12 4012

GRANT_DENY

0x00

Auto

2 4002

TAG_DESC

spaces

Auto

0 4000

Block

Hedder

TAG="AI"

O/S

Specified at the
time of order,
otherwise set below.

10.0

0.0

1061: m/s

4

10.0

0.0

1061: m/s

4

(Note) "Indirect" also can be set.