APPENDIX 2. INTEGRATOR (IT) BLOCK

Table A2.1 INTEG_TYPE

Name

Integration Method

Integration Range

Reset Trigger (Reset if one of the
following conditions is established)

Trip Output

UP_AUTO(1)

Counting up
Starting from "0"

-INF< Total <TOTAL_SP
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• OUT reaches TOTAL_SP.
• RESET_IN = 1
• OP_CMD_INT = 1

UP_DEM(2)

Counting up
Starting from "0"

-INF< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• RESET_IN = 1
• OP_CMD_INT = 1

DN_AUTO(3)

Counting down
Starting from
TOTAL_SP

0< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• OUT reaches "0."
• RESET_IN = 1
• OP_CMD_INT = 1

DN_DEM(4)

Counting down
Starting from
TOTAL_SP

-INF< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• RESET_IN = 1
• OP_CMD_INT = 1

PERIODIC(5)

Counting up
Starting from "0"

-INF< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• At the period specified by
CLOCK_PER
• OP_CMD_INT = 1

ϫ

DEMAND(6)

Counting up
Starting from "0"

-INF< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• RESET_IN = 1
• OP_CMD_INT = 1

ϫ

PER&DEM(7)

Legend

᭺: Trip output is made. ϫ: No trip output is made.

Counting up
Starting from "0"

-INF< Total <+INF
0< ATotal <+INF
0< RTotal <+INF
-INF< AccTotal <+INF

• At the period specified by CLOCK_PER
• RESET_IN = 1
• OP_CMD_INT = 1

ϫ

TA0203.EPS