6-9

6. OUTLINE

Natural Soft Rubber, EPDM Rubber lining:

Internal insertion type

Ceramics lining: Integral type

Sanitary Type: Internal insertion type

Replaceable Electrode Type

Electrode parts can be put into unit to facilitate replace-
ment or mounting at customer site.
The optional dedicated tool (F9807SK) is required.

Replaceable electrodes are available for the
following:

AXF standard:

Use

Lining

Wafer

Flange

25 to 300 mm
(1.0 to 12 in.)

25 to 400 mm
(1.0 to 16 in.)

General-
Purpose Use

Process

Connection

Available

Size

Electrode

Material

PFA/
Polyurethane
Rubber

JIS SUS316L
(AISI 316L
SS/EN
1.4404
equivalent)

(

*

1)

T06.EPS

Replacement model for earlier ADMAG or ADMAG AE:

Use

Lining

Flange

150 to 250 mm

(6.0 to 10 in.)

Process

Connection

Available

Size

Electrode

Material

PFA/
Polyurethane
Rubber

JIS SUS316L
(AISI 316L
SS/EN
1.4404
equivalent)

(

*

1)

T07.EPS

General-
Purpose Use

*1: If any other electrode materials are required, please

contact Yokogawa office.

Mounting/Shapes (Remote Flowtube):

• Electrical Connection: ANSI 1/2 NPT female

ISO M20

ϫ 1.5 female

JIS G1/2 (PF1/2) female

• Direction of Electrical Connection: The direction can be

changed even after delivery.

Note: In case of submersible types, an optional code DHC,

and sizes of 1100 mm or larger, the direction can not
be changed after delivery.

• Terminal Connection at Terminal Box: M4 size screw

Grounding:

Grounding resistance 100

Ω or less

* In case of explosion proof type except TIIS, follow the

domestic electrical requirements as regulated in each
country.

* In case of TIIS Flameproof type, refer to description of

“HAZARDOUS AREA CLASSIFCATION”.

Combined Converter:

• A remote flowtube for sizes of up to 400 mm can be

combined with the AXFA11 Converter or the AXFA14
Converter. If a combined converter is changed from
AXFA11 to AXFA14 or vice versa, a new meter factor
must be adjusted by flow calibrations.

• In case that size 250 mm (10 in.) or larger is used in low

conductivity or high concentration slurries, please use the
AXFA11 Converter.

• A remote flowtube for sizes of 500 mm or larger can be

combined with the AXFA11 Converter only.

• Maximum Cable Length:

Combination of AXF remote Flowtube and AXFA11:
up to 200 m (660 ft)
Combination of AXF remote Flowtube and AXFA14:
up to 100 m (330 ft)

HAZARDOUS AREA CLASSIFICATION

Refer to Chapter 8.

STANDARD PERFORMANCE

Accuracy

Note: The accuracy of a product before shipment is

defined as totalized value at the result of calibration
test in our water actual flow test facility.
Calibrated conditions in our water actual test facility
are as follows:

Fluid temperature;

20

± 10°C

Ambient temperature; 20

± 5°C

Length of straight runs;10 D or more on the

upstream side; 5 D or more
on the downstream side

Reference conditions; Similar to BS EN29104

(1993); ISO 9104 (1991)

Pulse Output:

PFA/Ceramics Lining;

Size mm

(in.)

V

Ͻ 0.3 (1)

Ϯ1.0 mm/s

Ϯ0.5 mm/s

Ϯ0.5 mm/s

0.3

Ϲ V Ϲ 10

(1) (33)

V Ͻ 0.15 (0.5)

V Ͻ 0.15 (0.5)

0.15

Ϲ V Ϲ 10

(0.5) (33)

0.15

Ϲ V Ϲ 10

(0.5) (33)

V Ͻ0.15 (0.5)

0.15

Ϲ V Ͻ1

(0.5) (3.3)

1

Ϲ V Ϲ10

(3.3) (33)

Ϯ0.35% of
Rate

Ϯ0.5 mm/s

Ϯ0.35% of
Rate

Ϯ0.35% of
Rate

2.5 (0.1)
to
15 (0.5)

250 (10)
to
400 (16)

25 (1.0)
to
200 (8.0)

Flow Velocity

V m/s (ft/s)

Flow Velocity

V m/s (ft/s)

Standard

Accuracy

(Calibration

code B)

High Grade

Accuracy

(Calibration

code C)

Ϯ0.18% of Rate

Ϯ 0.2mm/s
Ϯ0.2% of Rate

T08.EPS

Enhanced dual frequency excitation(Option code HF2):
Standard accuracy

Ϯ

1 mm/ s

Size 2.5 mm (0.1 in.) to 15 mm (0.5 in.)

1.2

1.0

0.8

0.6

0.4

0.35

0.2

0

0

1

2

6

8

10

V[m/s]

High grade Accuracy

High grade Accuracy

Standard Accuracy

F14.EPS

Pulse
Output
Accuracy

% of Rate

Size 25 mm (1.0 in.) to 400 mm (16 in.)

1.2

1.0

0.8

0.6

0.4

0.2

0

0.35

0

1

2

6

8

10

V[m/s]

F15.EPS

Pulse
Output
Accuracy

% of Rate

Standard Accuracy

High grade Accuracy

Advertising