3. OPERATION

IM 01C50T01-01E

3-6

Example: To set Pt100, 4-wire sensor as “

Sensor1

” input.

Also set a unit for Sensor1 as “

°

C

”.

YTA :
Snsr 1 config
1. Snsr1 Type
2. Snsr1 Wire 3 Wire
3. Snsr1 unit deg C

HELP

SAVE

HOME

ENTER

1

YTA :
Snsr1 type
Pt100(IEC751)
PT100(IEC751)
PT200(IEC751)
PT500(IEC751)
JPt100(JIS)

HELP

SEND

ABORT

ENTER

2

Press “

1

” to call up “

Snsr1 Type

display.

Call up the “

Snsr 1 config

” display.

Scroll with the up/down key until
designated sensor type is high-
lightened. Press

ENTER[F4]

to set

the type.

1. Device setup

3. Basic setup

4. Snsr 1 config

When selecting input type from T/C or mV, the
number of the wires is automatically set to “2 Wire”. It
is not necessary to change the setting in “Snsr1 Wire”.

YTA :
Snsr 1 config
1. Snsr1 Type
2. Snsr1 Wire 3 Wire
3. Snsr1 unit deg C

HELP

HOME

ENTER

3

YTA :
Snsr1 Wire
3 Wire
2 Wire
3 Wire
4 Wire

HELP

SEND

ESC

ENTER

4

Enter “

2

” to call up “

Snsr1 Wire

setting display.

Press down key until designated
wire number is high-lighted. Press

ENTER[F4]

.

Select “

3.Snsr1 unit

” to set the unit

for Sensor1.

Use

key to scroll the list

until designated unit is highlighted.
Press

ENTER[F4]

.

Press

SEND[F2]

to transfer the

data to the transmitter.
Check that

disappears.

YTA :
Snsr 1 config
1. Snsr1 Type
2. Snsr1 Wire 4 Wire
3. Snsr1 unit deg C

HELP

SEND

HOME

ENTER

5

YTA :
Sensor1 unit
degC
degC
Kelvin

HELP

DEK

ESC

ENTER

6

YTA :
Snsr 1 config
1. Snsr1 Type
2. Snsr1 Wire 4 Wire
3. Snsr1 unit deg C

HELP

SEND

HOME

ENTER

7

SEND

3.4.2 Process Variable Mapping

Process variable can be assigned as primary(PV),
secondary(SV), tertiary(TV) or fourth(4V) Variable
and can be monitored on Integral indicator or Handheld
terminal. The primary variable(PV) is output as a 4 to
20mA analog signal, and thus it is necessary to map
the variable as PV. Other variable can be left as “Not
Used” when they are not required.

Configuration of Sensor 1 (and Sensor 2 for YTA320)
must be done before changing the process variable
mapping. (See 3.4.1)