4. PARAMETERS LISTS

IM 01C50T01-01E

4-1

4.

PARAMETERS LISTS

Initial setting value marked with “ * ” is as of specified upon ordering.

Item

Selection/ Setting Range

Initial Setting

HART

Communicator

Up to 8 characters

Up to 8 characters

Up to 16 characters

Up to 32 characters

mm/dd/yy

0 to 16777215

°

C, K,

°

F, or

°

R (see note 1)

Set the calibration range using the keypad.

Value for 4 and 20 mA signal is set with actual input
applied.

0 to 99 seconds.

0 to 99%.

“Sensor1”, “Terminal Temperature(term)” or “Sensor1-
Term”.
For YTA320, above plus “Sensor2”, “Sensor2-Term”,
“Average” or “Differential” temperature.

Sensor1-Sensor2 or Sensor2-Sensor1.

Specify input type.

2, 3 or 4 wire.

°

C, K,

°

F, or

°

R. (See note 1).

Enable or disable

°

C, K,

°

F, or

°

R. (See note 1).

Internal CJC, Constant CJC

-10000 to 10000

Specify input type.

2, 3 or 4 wire.

°

C, K,

°

F, or

°

R. (See note 1).

Enable or disable

Enables/disables sensor backup mode.

Shows the backup status. (Waiting or Start.)

Enables the recovery to sensor1 during backup
operation.

Tag

Tag Ex

Descriptor

Message

Date

Snsr1(2)
snsr s/n

PV unit
(SV,TV,4V)

LRV/URV

Apply values

PV Damp
(SV,TV,4V)

PV Damp point

PV is
(SV,TV,4V)

Diff direction
(YTA320 only)

Snsr1 Type

Snsr1 Wire

Snsr1 unit

Snsr1 Match
Enbl (Note 3)

Term Unit

CJC Select

CNST CJC
Temp

Snsr2 Type

Snsr2 Wire

Snsr2 unit

Snsr2 Match
Enbl (Note 2)

Snsr Bkup

Bkup state&Cntl

Bkup Return
Snsr1

Memory

Process
Variable

Sensor1
Configuration

Terminal
Temperature

Sensor2
Configuration
(YTA320 only)

Engineering Unit

Range

Damping time
constant

Damping holding
point

Variable
mapping

Differential
Direciton

Sensor1 type

Sensor1 wire

Sensor1 unit

Enable sensor
match function

Terminal Temp.
unit

CJC Function

Sensor2 type

Sensor2 wire

Sensor2 unit

Enable sensor
match function

Sensor Backup
Function

T0401_1.EPS

Note 1:

°

F and

°

R are available only when option code /D2 is specified.

Note 2:

Appears only when Sensor Matching Function(/CM1) is specified.

—*

°

C*

LRV:0*
URV:100*

2 s

2%

PV:

Sensor1

SV(YTA320):

Sensor2

Sensor1-Sensor2

Pt100*

3 wire*

°

C*

disable

°

C*

Internal CJC

0

Pt100*

3 wire*

°

C*

disable

disable