3. OPERATION

IM 01C50T01-01E

3-7

YTA :
PV is Snsr1
SV is Term
TV is Not used
4V is Not used
Pressing 'OK' to change
them.

HELP

SAVE

ABORT

OK

1

YTA :
PV is
Snsr1
Snsr1
Snsr1-Term
Term

HELP

SEND

ABORT

ENTER

2

YTA :
PV is Snsr1
SV is Term
TV is Not used
4V is Not used
Pressing 'OK' will
send them.

HELP

SEND

ABORT

OK

4

The display in the left shows the
current setting of the map.
Press

OK[F4]

.

Calling up the “

Variable map

display.

Scroll with the up/down key until
the designated sensor type is high-
lightened. Press

ENTER[F4]

to

set the type. The selection is as
follows.
[For YTA110, YTA310]

Sensor1
Sensor1 - Terminal Temperature
Terminal Temperature

[For YTA320]
Above plus ;

Sensor2
Sensor2 - Terminal Temperature
Diff : Sensor2-Sensor1 or

Sensor1-Sensor2

Average : (Sensor1+Sensor2)/2

Follow the same procedures for
SV, TV and 4V. When you want to
leave the setting as it is, just press

ENTER [F4]

to move to the next

variable display. Pressing

ABORT[F3]

will cancel all the

previous procedures for mapping.

Press

OK[F4]

to send the new

setting to the transmitter.

1. Device setup

1. Process Variables

2. Variable setting

1. Variable map

YTA :
SV is
Not used
Snsr1
Snsr1-Term
Term
Not used

HELP

SEND

ABORT

ENTER

3

NOTE

Sensor type “Non-sntandard 1” “Non-standard 2”
are always shown, but cannot be used unless a
necessary function is pre-installed in the trans-
mitters upon shipment.

NOTE

1. When SV, TV or 4V are not required, it is

recommended to leave them as “

Not used

to improve the performance.

2. Each process variable, for example “

Sensor1

”,

can be assigned to only one variable. If

Sensor1

” is already set as PV, it cannot be

set as SV, TV or 4V simultaneously.

4. When “

Diff

”, “

Avg

”, “

Snsr1-Trem

”, or “

Snsr2-

Trem

” are selected, the sensor types to be

set for Sensor1 and Sensor2 should be
selected from any one of the following three
groups; Temperature sensor(T/C and RTD),
DC voltage or resistance. The combination(for
example, temperature sensor and DC voltage
input) would cause an incorrect computation
due to the different unit system and is not
allowed.

5. When “

Snsr1-Trem

” or “

Snsr2-Trem

” are

selected, DC voltage and resistance input
should not be set for Sensor1 or Sensor2.