4 pv range, Pv range -9, 1) changing the range with keypad – lrv, urv – Yokogawa Wireless Temperature Transmitter YTA510 User Manual

Page 22

Advertising
background image

3. OPERATION

IM 01C50T01-01E

3-9

3.4.4 PV Range

The range for PV corresponding to the 4 to 20mA
output signal is set at the factory before shipment.
Following are the procedures to change the range.

Example: To change the range from “

0 to 100

°

C

” to

50 to 200

°

C

”.

(1) Changing the range with Keypad

– LRV, URV –

YTA :
Hot key
1. Range values
2. Chng Wrt Protect

HELP

SAVE

ESC

ENTER

1

YTA :
Range values
1 PV LRV 0.00 degC
2 PV URV 100.00 degC
3 PV Unit degC
4 PV LSL -200.00 degC
5 PV USL 850.00 degC

HELP

DEL

ESC

ENTER

2

YTA :
LRV
0.0 degC
50.0

HELP

DEL

ESC

ENTER

3

YTA :
Range values
1 PV LRV 50.00 degC
2 PV URV 100.00 degC
3 PV Unit degC
4 PV LSL -200.00 degC
5 PV USL 850.00 degC

HELP

SEND

ESC

ENTER

4

YTA :
URV
100.00 degC
200

HELP

DEL

ESC

ENTER

5

YTA :
Range values
1 PV LRV 50.00 degC
2 PV URV 200.00 degC
3 PV Unit degC
4 PV LSL -200.00 degC
5 PV USL 850.00 degC

HELP

SEND

6

SEND

Press Hot key and call up “

Range

values

”.

Select the “

1. PV LRV

” to set the

Lower Range Value.
Setting limit dependig on the
selected sensor type is shown as

4. PV LSL

.” And “

5. PV USL

”.

Enter “

50

”, and press

ENTER[F4]

.

To set the Upper Range Value,
select the “

2 PV URV

”.

Setting limit is shown as “

4 PV

LSL

” and “

5 PV USL

”.

Press

SEND[F2]

to send the new

range value to the transmitter.
Confirm that disappears.

Enter “

200

” , and press

ENTER[F4]

.

NOTE

It is possible to set LRV>URV. This setting
reverses the 4 to 20 mA output signal.
Setting Conditions:

LSL <= LRV <= USL
LSL <= URV <= USL
|URV – LRV| >= Recom
mended Min. span

Advertising