2. HART COMMUNICATOR OPERATION

IM 01C50T01-01E

2-1

2.

HART COMMUNICATOR OPERATION

2.1 Conditions of Communica-

tion Line

2.1.1 Interconnection Between YTA

and HART Communicator

The HART communicator can interface with the
transmitter from the control room, the transmitter site,
or any other wiring termination point in the loop,
provided there is a minimum of 250W between the
connection and the power supply. To communicate, it
must be connected in parallel with the transmitter; the
connections are non-polarized. Figure 2.1 illustrates the
wiring connections for direct interface at the transmit-
ter site for the YTA. The HART communicator can be
used for remote access from any terminal strip as well.

HART communicator

HART

communicator

YTA

Distributor

Control room

Terminal board

Relaying
terminals

F0201.EPS

Figure 2.1 Interconnection Diagram

2.1.2 Communication Line

Requirements

Specifications for Communication Line:

Supply voltage

General use type; 16.4 to 42 V DC
Load resistance; 250 to 600

(Including cable resistance)
Minimum cable size; 24 AWG,

(0.51 mm diameter)

Cable type; Single pair shielded or

multiple pair with overall shield

Maximum twisted-pair length; 10,000 ft

(3,048 m)

Maximum multiple twisted-pair length;

5,000 ft (1,524 m)

Use the following formula to determine cable length
for a specific application;

L =

65

×

10

6

(R

×

C)

(C

f

+10,000)

C

where: L = length in feet or meters.

R = resistance in ohms, current sense

resistance plus barrier resistance.

C = cable capacitance in pF/ft or pF/m.
C

f

= Maximum shunt capacitance of field

devices in pF.