5 setting the auxiliary alarm function, Setting the auxiliary alarm function -7 – Yokogawa Button Operated DX2000 User Manual

Page 103

Advertising
background image

Measurement Channels and

Alarms

3-7

IM 04L42B01-01E

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

3.5 Setting the Auxiliary Alarm Function

Set the alarm display and output relays.
For a description of the functions, see section 1.2.

Setup Screen

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Alarm.

Setup Items

• Basic setting > Reflash

To set the reflash operation on the alarm output relay, select

On. The reflash function

is set on the first three output relays.

Setting

Description

Off

Reflash is not used.

On

Reflash is used. The relays are deactivated for approximately 500 ms.

On-1s

Reflash is used. The relays are deactivated for approximately 1 s.

On-2s

Reflash is used. The relays are deactivated for approximately 2 s.

• Basic setting > Rate of change
• Decrease

Set the interval for the rate-of-change calculation of the low limit on rate-of-change

alarm in terms of the number of sampled data points (1 to 32). The actual interval is
obtained by multiplying the value specified here by the scan interval.

• Increase

Set the interval for the rate-of-change calculation of the high limit on rate-of-change

alarm in the same manner as the interval for the low limit on rate-of-change alarm.

• Basic setting > Indicator

You can choose to make the alarm displays behave in the following ways. When you

use the alarm annunciator function (release number 3 or later), the setting follows the
annunciator sequence.

Settings

Description

Nonhold

Clears the alarm indication when the alarm condition is released (returns to

normal condition).

Hold

Holds the alarm indication until an alarm acknowledge operation is performed.

Advertising
This manual is related to the following products: