5 options, Options -11, App index – Yokogawa Button Operated DX2000 User Manual

Page 329: Vga output (/d5), Fail/status output relay (/f1), Fail/alarm output relay 22 outputs (/f2), Clamped input terminal (detachable) (/h2)

Advertising
background image

13-11

IM 04L42B01-01E

Specifications

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

13.5 Options

Alarm Output Relay (/A1, /A2, /A3, /A4, and /A5)

Item

Specifications

Action

Outputs relay contact signals from the terminals on the rear panel when alarms occur.

Number of outputs

2 outputs (/A1), 4 outputs (/A2), 6 outputs (/A3), 12 outputs (/A4), and 24 outputs (/A5)

Relay contact rating

250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (for resistance load)

Output format

NO-C-NC

Relay operation

Energized/deenergized, AND/OR, hold/non-hold, and reflash settings are selectable.

RS-232 Interface (/C2) and RS-422/485 Interface (/C3)

Item

Specifications

Connection

EIA RS-232(/C2) or EIA RS-422/485(/C3)

Protocol

Dedicated protocol or Modbus protocol

Synchronization

Start-stop synchronization

Transmission mode (RS-422/485)

Four-wire half-duplex multi-drop connection (1:N (N = 1 to 32))

Data rate

1200, 2400, 4800, 9600, 19200, or 38400 bps

Data length

7 or 8 bits

Stop bit

1 bit

Parity

Odd, even, or none

Handshaking

Off:Off, XON:XON, XON:RS, and CS:RS

Communication distance (RS-422/485)

1200 m

Modbus communication

Operation modes: Master or slave

VGA Output (/D5)

Item

Specifications

External display

Resolution:

640 × 480 dots (VGA)

Connector:

15-pin D-Sub

FAIL/Status Output Relay (/F1)

Item

Specifications

Relay operation assignment You can select which operations to assign to the two relays (release numbers 4 and later).
FAIL output

Relay contact output on CPU error

Relay operation

Energized during normal operation and de-energized on system error.

Status output

Output a relay contact signal when a selected condition occurs.
A combination of the following conditions can be selected:
Low memory, memory failure, media error, A/D hardware error, burnout detection, communication

error (Modbus master or client communication error), alarm occurrence

Relay operation

Relay is energized when a condition occurs.

Relay contact rating

250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (for resistance load)

FAIL/Alarm Output Relay 22 Outputs (/F2)

Item

Specifications

FAIL/status output

Same as /F1

Alarm output relay

Number of outputs: 22. Same as /A[ ] for other specifications.

Clamped Input Terminal (Detachable) (/H2)

Item

Specifications

Input terminal

Make the input section clamp input terminals (detachable).
Recommended wire size: 0.08 to 1.5 mm

2

(AWG 28 to 16)

Advertising
This manual is related to the following products: