• Alarm Hide Function

The alarm setting is displayed, but no indication is made when an alarm occurs. The

alarm is also not recorded in the alarm summary. The alarm is output to the relay
(/A[ ] option) or internal switch. This function can be set for each channel and each
alarm.

For the setting procedure, see section 3.6.

Alarm Output Relay Operation

Contact signals can be generated from alarm output relays (/A_ option) when alarms
occur. The alarm output relay operation can be changed.
For the setting procedure, see section 3.5.

Alarm

Alarm output relay

(Reflash on)

Alarm output relay

(Reflash off)

Channel 1

Channel 3

Channel 2

Energize or De-energize

AND/OR

Alarm

Channel 1

AND

Channel 2

OR

Alarm output relay

or

internal switch

NO

Energize

De-energize

C NC

NO C NC

NO C NC

NO C NC

NO C NC

NO C NC

When power

is shut down

NO: Normally Opened

C: Common

NC: Normally Closed

Normal

operation

When an alarm

is occurring

Alarm

Normal

Alarm

Normal

Reflash

(You can set AND/OR for the alarm output relay and internal

switch. For details about the internal switch, see the next

page.)

(when a relay is set to OR logic)

Normal

Reset

Relay

Action on

ACK

Relay

Action on

ACK

Occurrence

Activated

Deactivated

Activated

Deactivated

Activated

Deactivated

Release

or

Activated

Deactivated

or

Display

Alarm

Hold

Non-hold

Alarm output relay

Hold

Non-hold

Hold

Non-hold

Non-hold/Hold

Relay is activated

at the next scan

interval.

Relay is activated

when the next

alarm occurs.

Alarm ACK

Alarm ACK

500 ms, 1 s, or 2 s

1.2 Alarms

Advertising
This manual is related to the following products: