App-2

IM 04L42B01-01E

• Data Size per Sample
Display Data

(Number of measurement channels×4 bytes) + (Number of external input channels×4

bytes) + (number of computation channels×8 bytes) + 8 bytes (time data)

Event Data

(Number of measurement channels×2 bytes) + (Number of external input channels×2

bytes) + (number of computation channels×4 bytes) + 8 bytes (time data)

• Sampled Data Size per File
Display Data

Data size per sample × file save interval/sampling interval

The sampling interval is determined by dividing the trend interval (in seconds) by 30 (40

if the trend interval is 5 or 10 s).

Example 2: If the display data of 30 measurement channels, 240 external input
channels, and 10 computation channels is recorded with a trend interval of 30 min/div
(the sampling interval of display data is 60 s) and a file save interval of 1 day (24 h)

(30×4 bytes + 240×4 bytes + 10×8 bytes + 8 bytes)×24 hЧ60Ч60/60 s
= 1,168 bytes×24 hЧ60Ч60/60 s
= 1,681,920 bytes

Event Data

Data size per sample×data length/sample rate

Example 3: If the display data of 30 measurement channels, 240 external input
channels, and 10 computation channels is recorded with a sample rate of 1 s and data
length of 2 h

(30×2 bytes + 240×2 bytes + 10×4 bytes + 8 bytes)×2 hЧ60Ч60/1 s
= 588 bytes×2 hЧ60Ч60/1 s
= 4,233,600 bytes

Size per File

The size per file is the sum of the size of information other than the sampled data and the
size of the sampled data.

Display Data

Example 4: If recording under the conditions of examples 1 and 2

From examples 1 and 2, we obtain 60,938 + 1,681,920 = 1,742,858 bytes = 1.662 M

bytes

Event Data

Example 5: If recording under the conditions of examples 1 and 3

From examples 1 and 3, we obtain 60,938 + 4,233,600 = 4,294,538 bytes = 4.096 M

bytes

Appendix 1 File Size of Display Data and Event Data