Communication functions, Batch function – Yokogawa Button Operated DX2000 User Manual

Page 328

Advertising
background image

13-10

IM 04L42B01-01E

Communication Functions

Item

Specifications

Electrical and mechanical specifications

Conforms to IEEE 802.3 (Ethernet frames conform to the DIX specification).

Medium

Ethernet (10BASE-T)

Implemented protocols

TCP, IP, UDP, ICMP, ARP, DHCP, HTTP, FTP, SMTP, SNTP, Modbus, and DX-dedicated protocols

E-mail client

Automatically send e-mail at specified times.

FTP client

Automatically transfer data files to the FTP server.
Applicable files: Display data, event data, screen image data, and report data

FTP Server

Transfer files, delete files, manipulate directories, and output file lists of the DX.

Web server

Shows the DX display on a Web browser.

SNTP client

Inquires the time to the SNTP server and sets the DX.
Cannot be used after hour 0 on January 1st, 2036.

SNTP server

Outputs the DX time.
Time resolution: 5 ms
Cannot be used after hour 0 on January 1st, 2036.

DHCP client

Automatically obtain the network address settings from the DHCP server.

Modbus client

Reads data from another device and writes to the registers.

Modbus server

Loads measurement and computation channel data
Loads and writes external input channel data
Loads and writes communcation input data
Some control commands such as memory start
Modbus client register access limitations

Setting/Measurement server

Operate, set, and output data of the DX using a dedicated protocol.

Maintenance/test server

Outputs connection information and network information.

Instrument information server

Outputs information (serial number, model name, etc.) of the connected DX.

EtherNet/IP server

Can join an EtherNet/IP network as an adapter (server)
Loads measurement and computation channel data
Loads and writes external input channel data
Loads and writes communcation input data

Batch Function

Item

Specifications

Function

Data management using batch names. Enter text fields and batch comments in the data file.

Batch name

Added to the file name of the display data and event data.

Structure

Batch number (up to 32 characters) + lot number (up to 8 digits)

Text field

Adds text to the display data and event data. There are 24 available text fields for release numbers

3 and later. There are 8 available text fields for release numbers 2 and earlier. Up to 20 title

characters and 30 other characters can be entered per field.

Batch comment

Adds text to the display data and event data.

13.4 Other Standard Functions