Computation and Report Functions (/M1 and /PM1 Options)

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

• Report Channel number

The report is output in order by this number.

• Report CH > On/Off

Select

On for the report channels to be used.

• Report CH > Channel

Set the channel to assign to the report channel. All channels can be assigned, but

reports are not created for channels set to

Skip or Off even if they are assigned.

In the stacked bar graph display (see section 4.11 for details), report data is displayed

in the following groups. However, only channels that have the same unit as the first
channel in the group are displayed.

Report Group

DX2004, DX2008

DX2010, DX2020, DX2030,

DX2040, DX2048

1

R01 to R10

R01 to R10

2

R11 to R20

R11 to R20

3

-

R21 to R30

4

-

R31 to R40

5

-

R41 to R50

6

-

R51 to R60

• Report CH > Sum scale

Set the sum scale to

/s to /day to match the unit of the measured value.

Example: If the unit of the measured value is “m

3

/min,” select

/min.

Off: Sums as-is the measured data per scan interval.

• Handling of Overflow Data

Overflow data is handled in the same way as it is in statistical computations (TLOG

and CLOG).

See section 9.1.

Procedure

• Starting/Stopping the Report Function

Starting the memory sampling starts the report function. Likewise, stopping the

memory sampling stops the report function.

• Displaying the Reports

See section 4.5.

• Saving the Reports

See section 1.4.

9.5 Creating Reports