Troubleshooting

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Does the input meet
the specifications?

NO

NO

NO

NO

NO

YES

YES

YES

YES

• The error is large.
• The trend or digital values fluctuate.
• The trend is off the scale on either the 0% or 100% side.

YES

Change the input to meet the

specifications.

Is the input wiring correct?

• Attach the input terminal cover properly.
• Protect the input terminal from wind or
fans.
• Keep the temperature fluctuation near
the input terminal to a minimum.

• Adjust the span and range (section 3.3).
• If you use Calibration Correction (/CC1
option), check the set values for
correction points (section 3.9).

Is the range/span
setting appropriate?

Taking measures
against noise?

Is the environmental

temperature kept constant

(TC input)?

• Separate the input wiring from the

noise source.
• Ground the recorder.
• Ground the measured object properly.
• Insulate the TC from the measured object.
• Use shielded cables for input.
• Change the integral time of the input

A/D converter (section 3.1).
• Use moving average on the input

(section 3.4).

• Wire correctly (O.G.).
• Install the terminal block correctly.
• Fasten the terminal screws correctly.
• Insulate the RTD from the ground.
• If burnt, replace the TC.

Is the input wiring parallel

with other equipment?

YES

NO

NO

YES

Is the RJC setting correct

(TC input)?

• Stop the TC burnout upscale/downscale
function of other equipment.
• Ground the DX and other equipment
at one point.
• Disconnect parallel wiring
(use a double-element TC, for instance).

Set it correctly.

Contact your nearest YOKOGAWA
dealer.

Section 3.2

Section 12.1

O.G.: Operation Guide

11.2 Troubleshooting