13-15

IM 04L42B01-01E

Specifications

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Remote Control (/R1)

Item

Specifications

Number of input terminals

8

Input type

Isolated from the main circuitry through a photocoupler, built-in isolated power supply for the input

terminals, and shared common.

Input type and signal level

Voltage-free contact

Contact closed at 200 Ω or less and contact open at 100 kΩ or greater. The remote contact input

operation can be set to normal open or normal close (release number 3 or later)

Open collector

ON voltage: 0.5 V or less (sink current 30 mA or more), leakage current when OFF: 0.25 mA or less

Allowable input voltage

5 VDC

Signal type

Level or edge (250 ms or more)

Action

Executes a specified action by applying a given signal to the remote signal input terminal.
Action assignment: Set using the event action function

24 VDC Transmitter Power Supply (/TPS4 and /TPS8)

Item

Specifications

Number of loops

4 (/TPS4) or 8 (/TPS8)

Output voltage

22.8 to 25.2 VDC (under rated load current)

Rated output current

4 to 20 mADC

Max. output current

25 mADC (overcurrent protection operation current: approx. 68 mADC)

Allowable conductor resistance

RL ≤ (17.8 – minimum transmitter operation voltage)/0.02 A
where 17.8 V is the result obtained by subtracting the maximum drop voltage of 5 V when the

load shunt resistance is 250 Ω from the minimum output voltage of 22.8 V

Max. length of wiring

2 km (when using the CEV cable)

Insulation resistance

20 MΩ or more at 500 VDC between output terminal and ground

Dielectric strength

500 VAC (50/60 Hz, I = 10mA) for one minute between output terminal and ground
500 VAC (50/60 Hz, I = 10mA) for one minute between output terminals

Easy Text Entry (/KB1 and /KB2)

Item

Specifications

Remote control terminal (438227)

Operating temperature range

0 to 40°C

Operation humidity range

20% to 80% RH (at 5 to 40°C no condensation)

Power supply

3 VDC AA dry batteries × 2

Weight

Approx. 60 g (excluding the batteries)

External dimensions

170 (H) × 50 (W) × 23.7 (D) mm

Signal

Infrared

Combination with the DX

Number of units that can be controlled individually

Up to 32 units by setting the ID number

Communication distance

Up to 8 m from the front of the light receiving section of the DX (reference value)*

Directional characteristics

See the figure below (reference characteristics)*
* Varies depending on the operating environment such as the battery voltage and the presence

or absence of external light.

Standard accessories (/KB1)

Remote control unit, two alkaline dry batteries, and ID number label

Distance (m)

Horizontal

Vertical

0

0

0

30

15

15

10

10

5

5

1 1

-

30

-

45

-

60

45

60

90

-

90

Distance (m)

0

30

15

15

10

10

5

5

1 1

-

30

-

45

-

60

45

60

90

-

90

(+)

(+)

(-)

(-)

13.5 Options