Yokogawa Button Operated DX2000 User Manual

Page 336

Advertising
background image

13-18

IM 04L42B01-01E

Advanced Security Function (/AS1; release numbers 4 and later)

Item

Specifications

Login function

Only registered users can operate the DX.

Administrators

5 administrators

Users

90 users

User identification

User name, user ID, and password

Password management function

Password management feature that uses Windows Server 2003 or 2008 Active Directory

feature
Supports login authentication through a Kerberos authentication server

Audit trail function

Operation log storage

The operation history from the previous memory stop to the current memory stop is attached

to a data file.
Maximum operation logs: 2000

Change settings log and setup file storage

A setup file and change settings log are saved to the CF card when the settings are

changed.

Signature function (digital signature) Attaches approval information to measured data files.

Information that can be attached User name, date and time, pass/fail, comment
Number of signatures

Up to 3 per file

Signature record

Can be set for each user
The attached approval information cannot be deleted or changed.

Applicable files

Display data files and event data files in the internal memory
When the process type is “Batch”: Undivided data files (one data file per batch)
When the process type is “Continue”: Each data file

Measured Data File Protection

Measured data files are protected through operation logs, setup file storage, and encryption.

Data Formats and Extensions

Files that use this function have special extensions.
Display data: .DSD, event data: .DSE, setup data: .PEL, change settings log data: .TXT

Miscellaneous (main differences from DXs without the /AS1 option)

Data types

Display or event data only. Trigger mode cannot be used for event data.

Individual alarm ACK

ACK operations can be performed on individual alarms.

Alarm delay time

Up to 24 h

Event Action

The “PnlLoad” action is not available

Key lock

No

Deletion of external storage medium files

Not allowed.

Formatting of external storage media

Not allowed.

Loading of setup files

You can choose whether or not to load login information.

FAIL/status output relay (/F1 and /F2 options)

You can choose from five operations to assign to the two output relays.

Automatic messages

A message is written when the setting mode setup items are changed during memory

sampling.

Logs

There is no login log. There is an operation log and a change settings log.

13.5 Options

Advertising
This manual is related to the following products: