Yokogawa Button Operated DX2000 User Manual

Page 250

Advertising
background image

7-4

IM 04L42B01-01E

• Timer

Timer used by event action. Used also in the TLOG computation computation function.

* The timer cannot be changed while memory sampling or computation is in progress.

• Timer No.

Up to four timers (1 to 4) can be set.

When Using an Absolute Timer
• Mode

Select

Absolute.

• Interval

Select the interval from the available settings between 1min to 24h.

• Ref.time

Set the time in the range of hour 0 to hour 23.

When Using a Relative Timer
• Mode

Select

Relative.

• Interval

Set the interval in the range of 00:01 (1 min) to 24:00 (24 hours).

• Reset at Math Start

On: Resets the timer when computation is started. The resetting of the timer is not

considered to be a timeout. Even if the timer is used as an event, the action is not
executed.

• Match Time Timer

Set the time match condition used in event action.

* The condition cannot be changed while memory sampling or computation is in progress.

• Timer number

You can set up to four match time conditions (1 to 4).

• Kind

Settings

Description

Day

Set the time match condition of a day.

Week

Set the time match condition of a week.

Month

Set the time match condition of a month.

Year

The condition is matched once a year. This function is available for

release numbers 3 and later.

Set the items with check marks in the following table depending on the Kind setting.

Day

Week

Month

Year

Day

Day of week

Hour:Minute

Type

Setting



Month

• Month

Set the month.

• Day

Set the day.

• Weekday

Set the day of the week.

• Hour:Minute

Set the time in the range of 00:00 to 23:59.

• Timer action

Settings

Description

Single

Executes the action once when the condition is met.

Repeat

Executes the action at every specified time.

7.1 Setting the Event Action Function