Report Template Examples

• System Keyword Examples
Mixing a keyword and text

File header: $FileHeader$

Date and time: $DateTime$

File header: DX2000

Date and time: 2010/01/01 12:00:000

Mixing multiple keywords and text

Device number: $Serial$ File Header: $FileHeader$

Device number: ABCDEFG File Header: DX2000

• Report Data Keyword Examples

The following examples are for when the hourly report data for report channel R01 is

101, 102, 103, 104, and 105 and the hourly report data for report channel R02 is 201,
202, 203, 204, 205, and 206.

The $Repeat$ command applies to the closest keyword above the command in the

same column.

$ReportDataInst(Hour,R01)$

101

$Repeat$

102

$Repeat$

103

$Repeat$

→ 104

$ReportDataInst(Hour,R02)$

201

$Repeat$

202

$Repeat$

203

$Repeat$

204

$Repeat$

205

The $Repeat$ command applies to the keyword above it in the same column, even

when that keyword is not directly above the command.

$ReportDataInst(Hour,R01)$

101

$Unit(R01)$

°C

$Repeat$

102

$Unit(R01)$

°C

$Repeat$

$Unit(R01)$

103

°C

You can mix system keywords, report data keywords, and text. If the data specified by

a keyword does not exist, nothing is output.

$ReportDataInst(Hour,R01)$($Unit(R01)$)

101(°C)

$Repeat$

102

$Repeat$

103

$Repeat$($Unit(R01)$)

104(°C)

$Repeat$(°C)

105(°C)

$Repeat$

9.6 Creating a Report Template (Release numbers 4 and later)