Examples of Control Setup Operation

Control Setup Example 1: Single Loop Control

Object of Control and Description

SSR

CX2000

Electric
furnace

TC

1

2

3

4

5

6

7

8

9

10

26

27

28

29

30

21

22

23

24

25

16

17

18

19

20

11

12

13

14

15

DISP

/ENTER

LOOP1 PV

1

LOOP1 PULS

2

DIGITAL OUT1

3

DIGITAL OUT2

3

1

Loop 1 PV input terminal
of the control input terminal block

2

Loop 1 voltage pulse output terminal
of the control output terminal block

3

Relay contact output terminal
of the control output terminal block

High limit temperature alarm

Low limit temperature alarm

Voltage-pulse
control output

PV

Alarm output

• Loop number:

1

• PID constant:

P = 5%, I = 240 s, D = 60 s

• Control direction:

Reverse

• Input type:

TC K type

• Measurement span:

0 to 1200°C

• Output type:

Voltage pulse (cycle time: 3 s)

• Temperature setpoint: 700°C
• Alarm output:

PV high-limit alarm (high limit: 800°C), PV low-limit alarm (low
limit: 600°C)

Basic Control Settings

1.

From the operation display, open the basic control setting menu according to the
following procedure.
Press the

MENU key

(to switch to Set mode), then hold down the

FUNC key

for 3 s

(to switch to basic setting mode). Press the

Next 1/2 soft key

, then the

#10 soft key

(to select Control).

Menu (Setting mode (Control))

Menu (Basic setting mode 1/2)

Menu (Basic control setup menu)

Menu (Basic setting mode 2/2)