Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 16
Advertising

16
IM 04L31A01-02E
Select 1
(No need to set loop 2)
Select Cascade
Select Tem or
Press+Flow
4.
Press the
ESC key
to return to the basic control setting menu.
5.
Press the
#3 soft key
(Output processing).
6.
Press the
2 soft key
.
There are no control output settings on loop 1 (primary loop of cascade control).
7.
Press the
arrow keys
to move the cursor (blue) to the setup item box, press the
soft
key
of each value according to the following figure, and press the
DISP/ENTER key
.
Select 2
Select 4-20mA
Select Current-output
* No need to set
Cycle time
8.
Press the
ESC key
twice to return to the menu display (basic setting mode 2/2).
Examples of Control Setup Operation
Advertising