28

IM 04L31A01-02E

Note

You can select up to 10 channels from measurement channels (CH1 to CH20), computation

channels (CH31 to CH60), internal control channels (CH101 to CH118), and external control

channels (CH201 to CH248) using Channel setting.

Assignment of internal control channels (channels of internal loops)

The data of 6 loops is assigned to channel numbers as follows:

Loop 1 PV: 101, Loop 1 SP: 102, Loop 1 OUT: 103

...

Loop 6 PV: 116, Loop 6 SP: 117, Loop 6 OUT: 118

Assignment of external control channels (channels of external loops)

The data of 16 loops is assigned to channel numbers as follows:

External loop 1 PV: 201, External loop 1 SP: 202, External loop 1 OUT: 203

...

External loop 16 PV: 246, External loop 16 SP: 247, External loop 16 OUT: 248

Set the channels to assign them to a group according to the following rules.

Enter the channel number using two or three digits.

Separate each channel with a period.

Use a hyphen to specify consecutive channels.

Example: To assign CH1, CH3, CH5 to CH8, and CH101, enter 01.03.05-08.101.

Trend Display Example after Setup

SP

PV

OUT

Displaying the Trend of PV, SP, and OUT Values