Control Setup Example 2: Cascade Control

Object of Control and Description

CX2000

High limit temperature alarm

Low limit temperature alarm

High limit steam pressure alarm

Steam

Control valve

1

2

3

4

5

6

7

8

9

10

26

27

28

29

30

21

22

23

24

25

16

17

18

19

20

11

12

13

14

15

DISP

/ENTER

DIGITAL OUT1

4

DIGITAL OUT2

4

DIGITAL OUT3

4

1

Loop 1 PV input terminal
of the control input terminal block

2

Loop 2 PV input terminal
of the control input terminal block

3

Loop 2 current output terminal
of the control input terminal block

4

Relay contact output terminal
of the control output terminal block

Pt100

Tank

Pressure
transmitter

4 to 20 mADC
current output

Primary PV input

Alarm output

LOOP1 PV

1

LOOP2 PV

2

Secondary
PV input

LOOP2 mA

3

Primary loop of cascade control
• Loop number:

1

• PID constant:

P = 20%, I = 300 s, D = 60 s

• Control direction:

Reverse

• Input type:

RTD Pt100

• Measurement span: 0 to 100°C
• Temperature setpoint: 80°C
• Alarm output:

PV high-limit alarm (high limit: 90°C), PV low-limit alarm (low
limit: 70°C)

Secondary loop of cascade control
• Loop number:

2

• PID constant:

P = 120%, I = 20 s, D = 0 s

• Control direction:

Reverse

• Input type:

1-5 V

• Measurement span: 0 to 1.00 MPa
• Output type:

Current output (4-20 mA)

• Alarm output:

PV high-limit alarm (high limit: 0.90 MPa)

Basic Control Settings

1.

Display the basic control setting menu.
See “Control Setup Example 1” for the steps to show the menu.

2.

Press the

#1 soft key

(Control action, Input setting).

3.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of the value according to the following figure, and press the

DISP/ENTER key

.

Examples of Control Setup Operation