Switching between remote and local modes – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 31

Advertising
background image

31

IM 04L31A01-02E

Switching between Remote and Local Modes

The soft key menu does not show REM/LOC, if Control > Contact input-registration/
AUX(Alarm mode... > Remote setting is set to Off. Remote input cannot be used for the
target setpoint when the secondary loop of cascade control is selected or during program
control. Thus, there is no remote/local switching in these cases.

1.

Use the

arrow keys

to move the cursor to the desired control loop.

2.

Press the

REM/LOC soft key

.

A pop-up window for switching between remote and local appears.

Window for switching between
remote and local

3.

Select REMOTE or LOCAL using the

up and down arrow keys

.

4.

Press the

DISP/ENTER key

to confirm the changes.

Switching between Automatic and Manual for the Analog Retransmission Loop

You can switch the output mode for the control loop specified for analog retransmission.
When set to AUTO, the computed result of analog retransmission is output. When set to
MAN, you can set the direct output value.

1.

Use the

arrow keys

to move the cursor to the desired control loop.

2.

Press the

MODE soft key

.

A pop-up window switching between auto and manual appears.

Auto/manual switching window

3.

Select AUTO or MAN using the

up and down arrow keys

.

4.

Press the

DISP/ENTER key

to confirm the changes.

Switching the Operation Mode