Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 14

Advertising
background image

14

IM 04L31A01-02E

Setting Control Alarms in Setting Mode

1.

From the operation display, click the

MENU key

to display the control setting menu.

2.

Press the

#2 soft key

(Control alarm).

3.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of each value according to the following figure.

The numeric value of the alarm is entered using the pop-up window that appears by
pressing the

Input soft key

.

Select 1

Set to 600.0

Set to 800.0

Select DO002

Select DO001

Select On

Select PV-Low

Select PV-High

Select On

Select 1

4.

Press the

DISP/ENTER key

to confirm the settings.

Setting PID Parameters in Setting Mode

1.

From the operation display, click the

MENU key

to display the control setting menu.

2.

Press the

#4 soft key

(PID parameters).

3.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of each value according to the following figure.

The numerical values such as the SP are entered using the pop-up window that
appears by pressing the

Input soft key

.

Select 1

Set to 700.0

Select Reverse

Select 1

Keep the initial PID
values for Temp

4.

Press the

DISP/ENTER key

to confirm the settings.

Examples of Control Setup Operation