3.

Press the

arrow keys

to move the cursor (blue) to the Input type box, press the

PV1

soft key

, and set other parameters as shown in the figure below.

Check that 1 is
selected

Select 1-5V

Select PV1

Set to 0.00

Set to 300.00
Set to kg/h

4.

Press the

DISP/ENTER key

.

A confirmation window opens.

5.

Press the

DISP/ENTER key

to confirm the settings.

6.

Press the

arrow keys

to move the cursor (blue) to the Input type box, press the

PV2

soft key

, and set other parameters as shown in the figure below.

Check that 1 is
selected

Select 1-5V

Select PV2

Set to 0.00

Set to 30.00
Set to kg/h

7.

Press the

DISP/ENTER key

.

A confirmation window opens.

8.

Press the

DISP/ENTER key

to confirm the settings.

9.

Press the

arrow keys

to move the cursor (blue) to the Input type box, press the

PVrange soft key

, and set other parameters as shown in the figure below.

Set to 0.00

Set to 300.00
Set to kg/h

Check that 1 is
selected
Select PVrange

10.

Press the

DISP/ENTER key

.

A confirmation window opens.

11.

Press the

DISP/ENTER key

to confirm the settings.

Examples of Control Setup Operation