Program control function (/pg1 and /pg2 options), Program control function introduction, Operation mode during program control – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 35: Operations on the program selection display

Advertising
background image

35

IM 04L31A01-02E

Program Control Function (/PG1 and /PG2 Options)

Program Control Function Introduction

Program control function is used to ramp-up or ramp-down the SP according to a
program pattern. The number of program patterns that you can create with the CX2000
is as follows:

/PG1 option: 4

/PG2 option: 30

Up to 99 segments can be specified in a single pattern.

/PG1: 4 patterns
/PG2: 30 patterns

Segment

Time

SP

Operation Mode during Program Control

The following 4 types of operation modes are available.

Reset mode

Local operation mode

Program control mode

Hold operation mode

Switch

the loop

to program control.

Switch the loop to local.
End program to local.

The program control of all loops is stopped.

All event outputs are cleared (off).

When switched to local operation mode

even during program control,

fixed-point operation is carried out

according to the SPs specified locally.

The raising or lowering of the SP

according to the program pattern

during program control

is forcibly held such as through key operation.

Control operation is being carried out

according to the program pattern.

Program in operation

Clear hold.

Start

program control.

Execute hold.

Reset.

Stop all loops.

Start loop

operation.

Reset.
End program to reset.
Stop all loops.

Start

program control

Operations on the Program Selection Display (See the figure on the next page)

Displaying the Program Selection Display

On the control group display or control overview display, select

CONTROL

>

PROGRAM

from the screen selection menu.

Starting Program Control

Program control starts, and the screen switches to the Program Control Display.

1.

On the Program Selection Display, press the

RUN soft key

.

A pop-up window for starting the program control appears.

Window for starting
the program control

2.

Press the

DISP/ENTER key

.

Advertising