IM MX180-01E

The MX100 cannot be detected from the PC or cannot be detected wth the Search button.

Message

Correctve Acton

Reference

Page

The LINK LED does not turn ON.

The cable is broken.

Replace the Ethernet cable.

*

The LINK LED does not turn ON.

There is a problem with the hub.

Check the hub’s power supply. If it still does not work, replace

the hub and check the hub’s operation. Also, try to connect the

MX100 using the 10-Mbps fixed mode.

*

The LINK LED does not turn ON.

There is a problem with the PC.

Check whether the PC can connect to the network.

Replace the PC’s NIC.

*

The ACT LED does not turn ON.

There is a problem in the connection between

the hub and the MX100.

Check the hub’s power supply. If it still does not work, replace

the hub and check the hub’s operation.

Also, try to connect the MX100 using the 10-Mbps fixed mode.

*

The ACT LED does not turn ON.

There is a problem with the PC.

Check whether the PC can connect to the network.

Replace the PC’s NIC.

*

There is a problem in the network configuration.

The settings are not correct.

Check that the IP address, subnet mask, and default gateway

settings of the PC correspond to the MX100 settings.

2-7

There is a problem in the network configuration.

The setting changes have not taken effect.

Turn OFF the power to the PC and the MX100, and carry out

reconnection.

2-5, *

PC and the MX100 are not in the same segment.

Connect the PC and the MX100 in the same network segment.
If the PC and the MX100 are connected as shown in the

following figure, the Search button cannot be used to detect

the MX100. However, you can make a connection manually by

specifying the IP address.

2-7

MX

PC

Router

Network A

Network B

When using Windows XP, Windows Vista, or Windows 7, check

the firewall function.

2-1, App-1

* See the MX100 Data Acquisition Unit User’s Manual (IM MX100-01E).

The MX100 s detected by clckng the Search button, but connecton cannot be made.

Message

Correctve Acton

Reference

Page

The IP address is set to the default value.

The default value cannot be used to make the

connection.

Enter the correct IP address.

2-7

There is a problem in the network configuration.

Check that the IP address, subnet mask, and default gateway

settings of the PC and the MX100 settings are correct.

2-7

The PC software, main module style number,

and release number do not conform to the rule.

Check the release number of the PC software and the main

module style number, then upgrade the style.

[PC software release no.] ≥ [main module style no.]

**

** See the MX100 Data Acquisition Unit Operation Guide (IM MX100-02E).

MX100 cannot be connected usng the Calbrator

Message

Correctve Acton

Reference

Page

Attempting to make multiple connections.

Another software program is already connected.

Exit all other software programs.

-

The main module and input/output module style

numbers do not conform to the rule.

Check the release number of the PC software and the main

module style number, then upgrade the style.

[PC software release no.] ≥ [main module style no.] ≥

[input/output module style no.]

**

** See the MX100 Data Acquisition Unit Operation Guide (IM MX100-02E).