11 analog/pwm output settings, 11 analog/pwm output settings -60, 11 analog/pwm output settngs – Yokogawa PC-Based MX100 User Manual

Page 74: Analog output settngs

Advertising
background image

2-60

IM MX180-01E

2.11 Analog/PWM Output Settngs

Procedure

Analog Output Settngs

Transmission output

reference channel

Sets the output value upon

startup or error occurrence

Output range

selection

Minimum/Maximum value

of output span

Select the source action

Select output

or no output

Selection of output

action upon errors

Click here

Select the output

action upon startup

1.

Click Channel to show the Channel setup screen.

2.

Click the AO Channel tab.

3.

Select the Use check boxes for the AO channels you wish to output.

4.

Specify a channel operation of Transmission output or User output. If user output

is specified, you can enter settings in the monitor screen.

Only one of all the AO and PWM channels can be selected for user output.

5.

When transmission output is specified, enter the Reference channel.

The reference channel cannot be entered if the channel operation is user output.

6.

Select a range from the Range list box.

7.

Click the Min box or Max box under Span and enter the minimum or the maximum

value of the span.

8.

Click the Power ON box under Output Action and select Hold previous value or

Preset value.

9.

Click the Error box under Output Action and select Hold previous value or Preset

value.

10.

If you select Preset value under Output Action, click Preset value, and enter the

voltage or current.

Advertising